RC ELCB (Earth Leakage Circuit Breaker)
| Model Number:RC | Place of Origin:China |
| Price:-- | Packing:Export Carton |
| Transport mode:By Sea | Minimum Order:No request |
Online Postings: Products (66), offers (66)
Country/Territory: China
Business Type: Manufacture
Number of Employees: 501 ~ 1000 People
DESCRIPTION
It can open a circuit automatically in the case of an earth leakage fault between phase and earth or neutral greter or equal to 10mA,100mA,300mA or 500mA, It is used in domestic,commercial and industrial installation
EARTH FAULT INDICATOR
Mechanical indicator appearing on the front face of the RCCB is to be differed between tripping and off position yellow-tripped.
All the RCCBs are Protected against transient voltages(Lighting,line disturbances)and transient currents(from high cappacitive circuits)DC sensitive RCCB or time delay devices are availavle, Please consult us you also have the possibility to install the following accessories: electrical cover kit locking ket.
Standard: IEC1008, GB16916, BS EN61008
Rated Voltage(Un):
2 pole: 230V AC
4 pole: 400V AC
Rated Current(In): 25A, 40A, 63A
Rated Residual Operating Current(I△n): 30 100 300 500mA
Rated Residual non-Operating Current(I△no): 0.5I△n
Residual Current off-time: ≤ 0.1S
Minimum value of rated making and breaking capacity(Im): 1KA
Rated Conditional Short-Circuit Current(Inc):
In=25,40A Inc=1500A
In=63A Inc=3000A
Installation: On symmetrical Din Rail
skype: zhuanc