Air-Cooled Industrial Chiller

  • group nameAir-Cooled Industrial Water Chiller

  • Min Order1 piece

  • brand nameHERO-TECH

  • payment methodT/T

  • update timeThu, 28 Mar 2013 02:30:03 GMT

Paramtents

  • Color grey

Packging & Delivery

  • Min Order1 piece

Briefing

Air cooled industrial chiller
Features:
High efficiency
Accurate temperature control ±1°C
danfoss/sanyo compressor

Detailed

Air cooled industrial chiller
Model: HTI-10AD

Features:
High efficiency
Accurate temperature control ±1°C
Hitachi scroll type compressor
Error alarm for fault indication and Error code showed for checking the problem easily
Campact and elegant european design with Intelligent Digital Contral, easy for operation
Easy to install and maintain
One year warranty
Application
X-ray diffraction spectrometer
Wire cut / Spark erosion EDM (EDM=- Electron Discharge Machining)
Medical equipment
Machine tool
Induction hardening machine
High frequency welding machine
Hydraulic press
Pressure die casting
Furnaces
Power generators
Condenser cooling for low temperature test chambers
Injection moulding machine
Plasma spray / Coating machine
After coolers for compressed air drier
Chemical process plants
Dies & pigment manufacturing
Pharmaceutical industry
Electroplating plants
Anodizing plants
Food & beverage industry
Technical data

                                             Model
Item
HTI-10AD
nominal cooling capacity
kcal/h
22446
kw
26.1
input power
kw
10.47
power supply
3PH~380V/50HZ
refrigerant
type
R22
compressor
type
hermetic scroll
power(kw)
4.41*2
Cooling fan
cooling air flow(m3/h)
10000
evaporator
chilled fluid flow(m3/h)
4.47
inlet and outlet pipe diameter(inch)
1-1/2
pump
power(kw)
0.75
lift(m)
20
weight
kg
450
dimension
mm
1530*780*1430

Note:
1. Nominal cooling capacity is according to:
Inlet chilled fluid temperature: 12℃
Outlet chilled fluid temperature: 7℃
Inlet cooling air temperature: 30℃
Outlet cooling air temperature: 35℃
2. Working range:
The temperature range of chilled fluid is from 5℃ to 35℃;
Temperature difference between inlet and outlet chilled fluid is from 3℃ to 8℃.
It is better to use the chiller while the ambient temperature at or below 35℃.
We reserve the right to modify the above dimensions or parameters without further notice.

Delivery clauses under the trade mode
FOB, CFR, CIF, EXW
Acceptable payment methods
T/T, L/C, Westem Union