DPNL(CENB2L-32) earth leakage Circuit breaker 1P+N 25A 230V~ 50HZ/60HZ

  • group namecircuit breaker

  • Min Order12 piece

  • brand nameShangjing

  • modelCENB2L-32 C25

  • payment methodL/C, Western Union, T/T, Paypal

  • update timeTue, 28 Feb 2017 21:52:47 GMT

Paramtents

  • the brand name CENOE

  • the place of origin China

  • the warranty 2 years

  • Standards IEC1009:1991, GB6829-95, GB16917-1997

  • outline package size 43*24*24cm or as your requirments

Packging & Delivery

  • Size22cm x 8cm x 8cm

  • Weight0.15kg / piece

  • Min Order12 piece

Briefing

DPNL 1P+N 25A 230V~ 50HZ/60HZ Residual current Circuit breaker with over current, short circuit and Leakage protection

Detailed


Zhejiang CENOE electric co., LTD. Is  one of the professional enterprises collection of manufacturing, sales and researcher
So far, the 16 big series more than 600 kinds of specifications has been development and manufactured .
The mainly products include small circuit breaker, molded case circuit breaker, leakage circuit breaker, modular socket ,residual current circuit breaker, intelligent universal type circuit breaker, control and protection switch, dual power automatic transfer switch, etc.
 
The company introduces the advanced production equipment and perfect testing facilities, set up a technology research center and development team, And has passed ISO9001 quality system certification, the European Union CE certification and national compulsory CCC certification, the company also owns four national patent certificate, all products are quality of contractor shall be conducted by the people's insurance company of China.Part of the product performance has reached the international leading level, products are exported to Europe, America, Middle East and other countries and regions.
 
CENOE in global markets, will follow a win-win concept and hand in hand with you, innovation value, achievement industry mode


DPNL 1P+N 25A 230V~ 50HZ/60HZ Residual current Circuit breaker(CENB2L-32) used in AC 50/60 hz,rated voltage 230 v, rated current 6 a to 32 a single residential line, with overload, short circuit and earth leakage protection function.Phase line and zero line cut off at the same time, which can effectively prevent wiring errors and system fault caused the accident.CENB2LE - 32 filtering device of residual current circuit breaker, can effectively prevent maloperation work trip by reason of equipment starting, line interference caused by instantaneous pulse voltage and current reference 
This product conforms to the IEC1009:1991, GB6829-95, GB16917-1997 standard requirement.

specifications

Number of Poles

crust class rated current

IP+N

32A

Rated Current(A)

25

Rated Residual Operating Current (I/En)(mA)

30

Rated Residual Non-Operating Current (I/En)(mA)

15

Rated Voltage (V)

230

Residual Current Off-time

0.1S

breaking capacity

4000A

Overload Trip Characteristic

Testing

Current(A)

Rated

current(A)

Limited

Time

The expected

Result

Start

Situation

Note

1.13In

all

T1h

Non-trip

Cold state

 

The current rise steadily to a fixed value within 5s

1.45 In

all

T1h

Trip

Heat state

2.55 In

all

1S<t<60s

Trip

Cole state

 

5 In

all

T0.1s

Non-trip

Cold state

Open the supplementary switch, connect the power

10 In

all

T0.1s

trip

Cole state

Open the supplementary switch, connect the power

 

Switch to the left with T type button is used to test the performance of the switch for a month, such as leakage sensitivity, etc., Specific operation as follows:

 1: press the test button once a month, check the movement of leakage protection device,

2: when leakage protective device movement , the device have red mechanical instructions below

3:  when re-closing circuit breaker, protection device automatically reset