220V 16KW EVI Monobloc Heat Pumps(SHAW-16EVIM)

  • group nameEVI Air Source Heat Pumps

  • Min Order5 piece

  • brand nameSuoher Inverter Heat Pumps Manufacturer

  • modelSHAW-16EVIM

  • payment methodL/C, T/T

  • update timeMon, 29 Apr 2024 05:10:18 GMT

Paramtents

  • Net dimensions 1110*460*1250(mm)

  • Packing dimensions 1180*530*1395(mm)

  • Power supply 220V/1PH/50Hz

  • Air flow 6500m³/h

  • Fan rated power 90W*2

  • Water pressure drop 27Kpa

Packging & Delivery

  • Size118cm x 53cm x 140cm

  • Weight158.00kg / piece

  • Min Order5 piece

Briefing

Low ambient temperature 16kW EVI monobloc heat pumps for heating, hot water and cooling in summer.

Detailed

1.  Heating and hot water modes.
2. Heating capacity 11kw, 12kw, 16kw, 18kw, 20kw, 34kw, 40kw.
3. Work at down to -25DegC.
4.  Electronic expansion valve for main circuit and EVI circuit.
5.  Receives ON/OFF signal from thermostat, master controller, smart grilletc to save more energy.
6. Heating curves for more comfortable temperature and more energy-saving.
7. Monobloc type.
8. Copeland scroll EVI compressor.
9. With compressor heater.
10.  With bottom plate heater.
11.  With 3kw back-up electric heater.
12.  With energy class A circulating pump.
13.  With control for 3-way valve to switch between heating circuit and hotwater circuit.
14.  With water flow switch.
15.  We offer OEM service including back-up heater, circulating pump, casingdesign, painting color etc.

Model

 

SHAW-16EVIM

SHAW-18EVIM

SHAW-20EVIM

Power supply

/

220V/1PH/50Hz

380V/3PH/50Hz

380V/3PH/50Hz

Refrigerant

/

R407C

R407C

R407C

Heating capacity 1

KW

15.5

17.9

20.9

Heating power input  1

KW

3.48

4.03

4.76

COP 1

/

4.45

4.44

4.39

Heating capacity 2

KW

11.9

13.4

15.6

Heating power input  2

KW

3.69

4.18

4.89

COP 2

/

3.22

3.21

3.19

Heating capacity 3

KW

8.9

10.2

11.9

Heating power input  3

KW

3.60

4.16

4.94

COP 3

/

2.47

2.45

2.41

Heating capacity 4

KW

7.7

9.0

10.5

Heating power input  4

KW

3.55

4.11

4.87

COP 4

/

2.17

2.19

2.16

Heating capacity 5

KW

13.10

15.10

17.60

Heating power input  5

KW

5.46

6.29

7.39

COP 5

/

2.40

2.40

2.38

Max. water temperature

60

60

60

Rated water temperature

55

55

55

Water flow

m3/h

2.40

3.10

3.60

Condenser

 

tube-in-shell

tube-in-shell

tube-in-shell

Water pressure drop

Kpa

27

28

29

Water connections

Inch

1

1

1

Built-in water flow switch

 

paddle type

paddle type

paddle type

Built-in water pump

 

NO

NO

NO

Built-in electric heater

 

NO

NO

NO

Built-in auto air vent

 

NO

NO

NO

Built-in water expansion vessel

 

NO

NO

NO

Compressor

Brand

Copeland (EVI)

Copeland (EVI)

Copeland (EVI)

Quantity

1

1

1

Type of defrosting

/

Reverse circulation

Reverse circulation

Reverse circulation

Fan quantity

 

2

2

 

Air flow

m³/h

6500

6500

6500

Fan rated power

W

90*2

90*2

90*2

Noise

dB(A)

55

55

55

Net weight

kg

143

150

150

Gross weight

kg

158

165

165

Net dimensions

mm

1110*460*1250

1110*460*1250

1110*460*1250

Packing dimensions

mm

1180*530*1395

1180*530*1395

1180*530*1395

 

1. Unit working temperature : -25℃ to 43℃
2. 
1)Test condition: ambient temp: 7℃/6℃, water inlet/outlet: 30℃/35℃
2) Test condition: ambient temp: -2℃/-1℃, water inlet/outlet: 30℃/35℃
3)Test condition: ambient temp: -15℃/-℃, water inlet/outlet: 30℃/35℃
4)Test condition: ambient temp: -20℃/-℃, water inlet/outlet: 30℃
5)Test condition: ambient temp: 7℃/6℃, water inlet: 58℃