Thermal Relay

  • group nameThermal Relay

  • Min Order1 piece

  • modelLRD

  • update timeThu, 18 Aug 2011 14:44:26 GMT

Packging & Delivery

  • Min Order1 piece

Briefing

Differential thermal overload relays for using with fuse

Detailed

Differential thermal overload relays for using with fuse
Compensated relays manual or automatic reset, with relay trip indicator, for AC. or DC.
Relay setting range   For using with Reference Weight
aM gG BS88 contactor LC2 -    
A A A A      
Class 10A (1) with connection by screw clamp teminals
0.10 ... 0.16 0.25 2 - D09 ... D38 LRD - 01 0.124
0.16 ... 0.25 0.5 2 - D09 ... D38 LRD - 02 0.124
0.25 ...0.40 1 2 - D09 ... D38 LRD - 03 0.124
0.40 ... 0.63 1 2 - D09 ... D38 LRD - 04 0.124
0.63 ... 1 2 4 - D09 ... D38 LRD - 05 0.124
1 ... 1.7 2 4 6 D09 ... D38 LRD - 06 0.124
1.6 ... 2.5 4 6 10 D09 ... D38 LRD - 07 0.124
2.5 ... 4 6 10 16 D09 ... D38 LRD - 08 0.124
4 ... 6 8 16 16 D09 ... D38 LRD - 10 0.124
5.5 ... 8 12 20 20 D09 ... D38 LRD - 12 0.124
7 ... 10 12 20 20 D09 ... D38 LRD - 14 0.124
9 ... 13 16 25 25 D12 ... D38 LRD - 16 0.124
12 ... 18 20 235 32 D18 ... D38 LRD - 21 0.124
16 ... 24 25 50 50 D25 ... D38 LRD - 22 0.124
23 ... 32 40 63 63 D25 ... D38 LRD - 32 0.124
30 ... 38 50 80 80 D32 and D38 LRD - 35 0.124
17 ... 25 25 50 50 D40 ... D90 LRD - 322 0.510
23 ... 32 40 63 63 D40 ... D90 LRD - 3353 0.510
30 ... 40 40 100 080 D40 ... D90 LRD - 3355 0.510
37 ... 50 63 100 100 D40 ... D90 LRD - 3357 0.510
48 ... 65 80 100 100 D50 ... D90 LRD - 3359 0.510
55 ... 70 80 125 125 D50 ... D90 LRD - 3362 0.510
63 ... 80 100 125 15 D65 and D96 LRD - 3363 0.510
80 ... 104 125 160 160 D80 and D96 LRD - 3365 0.510
80 ... 104 125 200 160 D115 and D150 LRD - 4365 0.900
95 ... 120 160 200 200 D115 and D150 LRD - 4367 0.900
110 ... 140 100 250 200 D150 LRD - 4369 0.900
80 ... 104 125 160 160 (2) LRD - 33656 1.000
95 ... 120 160 200 200 (2) LRD - 33676 1.000
110 ... 140   250 200 (2) LRD - 33696 1.000
Class 10A (1) with spring teminal connections (for direct mounting on the contactor only)
0.10 ... 0.16 0.25 2 - D09 ... D38 LRD - 013 0.140
0.16 ... 0.25 0.5 2 - D09 ... D38 LRD - 023 0.140
0.25 ... 0.40 1 2 - D09 ... D38 LRD - 033 0.140
0.40 ... 0.63 1 2 - D09 ... D38 LRD - 043 0.140
0.63 ... 1 2 4 - D09 ... D38 LRD - 053 0.140
1 ... 1.7 2 4 6 D09 ... D38 LRD - 063 0.140
1.6 ... 2.5 4 6 10 D09 ... D38 LRD - 073 0.140
2.5 ... 4 6 10 6 D09 ... D38 LRD - 083 0.140
4 ... 6 8 16 16 D09 ... D38 LRD - 103 0.140
5.5 ... 8 12 20 20 D09 ... D38 LRD - 123 0.140
7 ... 10 12 20 20 D09 ... D38 LRD - 143 0.140
9 ... 13 16 25 25 D12 ... D38 LRD - 163 0.140
12 ... 18 20 235 32 D18 ... D38 LRD - 213 0.140
16 ...24 25 50 50 D25 ... D38 LRD - 223 0.140
Thermal overload relays for using with unbalanced loads                                                                   
Class 10A (1) with connection by screw clamp terminals                                                                  
Change the prefix in the referenes above from LRD (except LRD - 4...) to LRD - D.                               
Example: LRD - 01 becomes LR3 - D01.                                                                                       
Thermal overload relays for using on 1000V supplies
Class 10A (1) with connection by screw clamp terminals
(1)Standard IEC947 - 1 specifies a tripping time for 7.2 times the setting current IR: class 10A : between 2 and 10 seconds.
(2) Independent mounting.