group nameEarth Leakage Circuit Breaker
Min Order1 piece
update timeFri, 08 Jul 2011 16:54:13 GMT
Min Order1 piece
APPLICATION:
This series of circuit breakers is suitable for AC 50Hz, rated voltage up to 230V/400V, rated current up to 50A, used to protect person against indirect contact, and protect circuitry of buildings or similar line against overload or short-circuit. It also can be over-current protection the equipment against fire caused by lasting earth fault due to the non-operation of over-protection device. In addition, it can be used to switch the circuitry infrequently under normal condition.
The products comply with GB16917&IEC61009.
CLASSIFICATION:
1. Main specifications
Divide according to the rated current In:6A, 10A,16A,20A,25A,32A,40A and 50A.
Divide according to the rated residual operating current: 30m A ,50 m A,100 m A and 300 m A;
Divide according to the pole number and number of current loops: Single-pole two-wire leakage circuit breaker; Two-pole leakage circuit breaker; Three-pole leakage circuit breaker; Three-pole four-pole leakage circuit breaker
Four-pole leakage circuit breaker.
2. Technical parameters:
Rated short-circuit making and breaking capacity Im: 6000A(In is equal or less than 32A),
4000A(D type or 32A is less than In is equal or less than 50A);
Rated residual making and making and breaking capacity I?m:2000A;
Rated residual non-operating current I?no:0.5I?n;
Break time of residual current operation.
Over-current protection characteristics.
Mechanical and electrical life:2000 times;
Characteristic curve of release.