Residual Circuit Breaker with Overload Protection GL018 Series

  • group nameResidual Circuit Breaker

  • Min Order1 piece

  • update timeThu, 25 Aug 2011 14:30:53 GMT

Packging & Delivery

  • Min Order1 piece

Briefing

Residual Circuit Breaker with Overload Protection
APPLICATION
GL018 series residual circuit breaker with overcurrent p

Detailed

Residual Circuit Breaker with Overload Protection

APPLICATION
GL018 series residual circuit breaker with overcurrent protection, it's in accordance with standards of
IEC61009, GB16917. 2P switching of ph&N, Phase only protected against overloads and short circuits.
it is used in commercial, industrial and domestic electrical distribution systems.
It mustn't be used as the sole means of providing protection against direct contact. The RCBO
incorporates a residual current operated electromagnetic release which operates without any auxiliary
source of suppl to open a circuit automatically in the case of an earth leakage fault between phase and
earth greater than or equal to In.The RCBO combined MCB&RCCB provides:
Protection against indirect contact
Complementary protection against direct contact
Protection for the installation against in sulation faults

TECHNICAL SPECIFICATION 
Type GL018D GL018U
Number of poles 1P+N
Rated current(In) 1, 2, 3, 4, 6, 10, 16, 20, 25, 32,40A
Rated operating current(I△n) 15, 30, 100, 300mA
Leakage dead current(I△no) I△no=0.5I△n
Rated voltage(Un) AC 230(240) V
Residual current off-time ≤0.1s
Ultimate short-circuit breaking capacity(Icn) 10000A
Terminal protection IP20