group namePCB chiller
Min Order1 piece
brand nameHERO-TECH
payment methodT/T
update timeThu, 28 Mar 2013 02:28:21 GMT
Casing Color grey
Compressor Double original Sanyo
Refrigerant R22 or R407C or others
control method capillary or Expansion valve
Min Order1 piece
PCB CHILLERS adopt American and Japanese brand absolutely new compressors,featuring built-in safety protection,low noise,low electricity consumption,and long service life.
Model [HTI-**] | 6A | 8AD | 10AD | 12AD | 15AD |
| ||||||||||
Item |
| |||||||||||||||
nominal cooling capacity | kcal/h | 13115 | 17630 | 22446 | 25585 | 35948 |
| |||||||||
kw | 15.25 | 20.5 | 26.1 | 29.75 | 41.8 |
| ||||||||||
input power | kw | 6.33 | 8.29 | 10.47 | 11.82 | 16.42 |
| |||||||||
power supply | 3PH ~ 380V 50HZ |
| ||||||||||||||
refrigerant | type | R22 |
| |||||||||||||
type of control | capillary | thermostatic expansion valve |
| |||||||||||||
compressor | type | hermetic scroll (piston) |
| |||||||||||||
power(kw) | 5.2 | 3.52*2 | 4.41*2 | 9.82 | 7.2*2 |
| ||||||||||
condenser | type | finned copper tube + low noise outer rotor fan |
| |||||||||||||
evaporator | type | water tank with coil (shell and tube) |
| |||||||||||||
chilled fluid flow(m 3 /h) | 2.63 | 3.52 | 4.47 | 5.12 | 7.1 |
| ||||||||||
volume(L) | 70 | 120 | 200 | 200 | 270 | |||||||||||
pump | power (kw) | 0.75 | 0.75 | 0.75 | 1.1 | 1.5 |
|
|
|
|
|
|
| |||
lift(m) | 20 | 22 | 20 | 20 | 20 |
|
|
|
|
|
|
|
| |||
weight | kg | 180 | 310 | 450 | 530 | 750 |
|
|
|
|
|
|
|
| ||
dimension | mm | 1140*560*1040 | 1300*720*13100 | 1530*780*1430 | 1530*780*1430 | 1800*990*1680 |
|
|
|
|
|
|
|
| ||
Note: 1. nominal cooling capacity is according to: |
| |||||||||||||||
Inlet chilled fluid temperature: 12 | ||||||||||||||||
Outlet chilled fluid temperature: 7 | ||||||||||||||||
Inlet cooling air temperature: 30 | ||||||||||||||||
Outlet cooling air temperature: 35 | ||||||||||||||||
2. working range: | ||||||||||||||||
The temperature range of chilled fluid is from 5 to 35; | ||||||||||||||||
Temperature difference between inlet and outlet chilled fluid is from 3 to 8. | ||||||||||||||||
The machine should be used when the ambient temperature at or below 35. | ||||||||||||||||
We reserve the right to modify the above dimensions or parameters without further notice. |