Water Cooled Screw Chiller

  • group nameWater-Cooled Screw Chiller

  • Min Order1 piece

  • brand nameHERO-TECH

  • payment methodL/C, T/T

  • update timeWed, 27 Mar 2013 22:24:57 GMT

Paramtents

  • Casing color grey

  • Evaporator Shell and Tube

  • Compressor brand Bitzer or Hanbell

  • Compressor type Semi- hermetic screw

  • Refrigerant R22, R407C or R134a

  • Control method Thermostatic expansion valve

Packging & Delivery

  • Min Order1 piece

Briefing

Introduction of water cooled screw type chiller adopts world famous brand compressor--bitzer and hanbell

Detailed

Introduction of water cooled screw type chiller unit
1. adopts world famous brand compressor--bitzer and hanbell which efficiency is 20% to 30% higher than those common ones.
2.Capacity control can apply to four step,three step and stepless control system;
3.High efficiency,low noise and small vibration;
4.R22,R134a,R407c can be chosen to meet your demand;
Technical data

Model [HTS-**]

40W

50W

60W

75W

85W

100W

10W

Item

nominal cooling capacity

kcal/h

103200

133300

150500

202100

232200

253700

318200

kw

120

155

175

235

270

295

370

input power

kw

30

36

41

56

61

70

85

max. running current

A

71

84

96

131

142

188

200

power supply

3PH~380V 50HZ

refrigerant

type

R22 /R407c

refrigerating circuit

1

type of control

thermostatic expansion valve

compressor

type

semi-hermetic screw

quantity

1

start-up mode

Y- △

capacity control

0-25-50-75-100

condenser

type

shell and tube

evaporator

type

shell and tube

quantity

1

chilled fluid flow(m 3 /h)

21

27

30

40

46

51

64

safety protection

compressor over temperature, unit overload, high and low pressure, flow switch, phase sequence, phase-missing, antifreezing

net weight

kg

1400

1600

1800

2050

2250

2500

3200

running weight

kg

1600

1800

2000

2350

2550

2850

3600

Note: 1. nominal cooling capacity is according to:

Inlet chilled fluid temperature: 12℃.Outlet chilled fluid temperature: 7℃.

Inlet cooling water temperature: 30℃.Outlet cooling water temperature: 35℃.

2. working range:

The temperature range of chilled fluid is from 5℃ to 20℃;
Temperature difference between inlet and outlet chilled fluid is from 3℃ to 8℃.
The temperature range of cooling water is from 22℃ to 35℃;

Temperature difference between inlet and outlet cooling water is from 3℃ to 8℃.

We reserve the right to modify the above dimensions or parameters without further notice.

Delivery clauses under the trade mode
FOB, CFR, CIF, EXW
Acceptable payment methods
T/T, L/C, Westem Union
Contact Suppliers

Follow this Suppliers