group nameWater-Cooled Industrial Water Chiller
Min Order1 piece
brand nameHERO-TECH
payment methodT/T
update timeWed, 27 Mar 2013 23:02:46 GMT
Color grey
Compressor Doule sets, Danfoss Performer
Refrigerant R22
other equipment require work together Cooling tower and cooling water pump
Min Order1 piece
Industrial Water-Cooled Chiller
Features:
Copeland Scroll type compressor
±1°C precise temperature control
High cooling efficiency
Intelligent temperature control system
Easy for operation and installation
Compact design and elegant appearance
Technical data:
model [HTI-**] | 20WD | 25WD | 30WD | 40WD | 50WD | 60WD | |
nominal cooling capacity | Kcal/h | 51772 | 58738 | 83420 | 104490 | 134332 | 158240 |
Btu/h | 208132 | 233040 | 330964 | 414558 | 522718 | 627896 | |
KW | 61 | 68.3 | 97 | 121.5 | 153.2 | 184 | |
US.RT/h | 17.42 | 19.51 | 27.71 | 34.71 | 43.77 | 52.33 | |
input power | KW | 19.71 | 21.89 | 31.19 | 37.95 | 48.5 | 59.3 |
power supply | 3PH~380V 50HZ | ||||||
refrigerant | type | R22 | |||||
type of control | thermostatic expansion valve | ||||||
compressor | type | hermetic scroll | |||||
power (KW) | 8.3×2 | 9.82×2 | 13.72×2 | 17.1x2 | 21.5x2 | 26.9×2 | |
condenser | type | shell and tube | |||||
cooling water flow (m3/h) | 13.9 | 15.8 | 20.5 | 26.7 | 33 | 40.9 | |
inlet and outlet pipe diameter | 2" | 2 1/2" | 3" | 3" | 4" | 4" | |
evaporator | type | water tank with coil | |||||
chilled fluid flow (m3/h) | 10.3 | 11.76 | 16.7 | 20.92 | 26.3 | 31.6 | |
tank volume (L) | 330 | 350 | 450 | 580 | 620 | 620 | |
inlet and outlet pipe diameter | 2-1/2" | 2-1/2" | 2-1/2" | 3" | 3" | 4" | |
water pump | power (KW) | 2.25 | 2.25 | 3.75 | 3.75 | 5.5 | 5.5 |
lift (m) | 20 | 20 | 22 | 22 | 23 | 23 | |
safety protection | compressor over temperature, over current, high and low pressure, over temperature,phase sequence, phase-missing, exhaust overheating | ||||||
dimension | length (mm) | 1700 | 1700 | 1880 | 2000 | 2000 | 2150 |
width (mm) | 810 | 810 | 910 | 980 | 980 | 1100 | |
height (mm) | 1620 | 1620 | 1800 | 1960 | 1960 | 2150 | |
weight | Kg | 820 | 900 | 1150 | 1200 | 1380 | 1450 |
Note: 1. nominal cooling capacity is according to: Inlet chilled fluid temperature: 12℃ Outlet chilled fluid temperature: 7℃ Inlet cooling air temperature: 30℃ Outlet cooling air temperature: 35℃ 2. working Range: The temperature range of chilled fluid is from 5℃ to 35℃; Temperature difference between inlet and outlet chilled fluid is from 3℃ to 8℃. The temperature range of cooling water is from 18℃ to 37℃; |